SAFETY PRECAUTIONS1. Check if an electric leakage occurs in the set.2. When servicing current applying parts, unplug prior toservicing.3. In case of t
COMPRESSOR AND ANOTHER ELECTRIC COMPONENTSSeparate the PTC-STARTER fromthe Compressor and measure thevoltage between M and C of theCompressor.Equal to
PTCPoor starting or nooperating of theCompressor.4DFirst, separate the PTC fromthe Compressor and check thevoltage between NO 5 and 6in the PTC with a
EXPLODED VIEW-14-
HOME DEPOT(HDP) Electrical SpecificationITEM GR-051SF GR-131SF GR=151SFBUYER MODEL NAME GR_051SF GR_131SPF GR-151SPFRATED INPUT(W) 70+15% 70+15% 70+15
In case that a considerable leakage occurs and to stop thevacuum pump will be necessary and add a small quantityof Freon to the system, if vacuum shou
AIR RECHARGING IN COMPRESSORTest the refrigeration system by connecting it electricallybefore refilling operation. This is necessary to ascertain thef
In case that a considerable leakage occurs and to stop thevacuum pump will be necessary and add a small quantityof Freon to the system, if vacuum shou
SPECIFICATIONSITEMS SPECIFICATIONSDOOR TYPE 1 DOORNET CAPACITY 94 lCONDENSER TYPE WALL CONDENSER(FLUSH BACK)DEFROSTING SYSTEM MANUALTEMPERATURE CONTRO
DISASSEMBLYA. DOOR1. Loosen 3 screws holding an upper hinge to separate thedoor body. (Figure 7)Figure 7B. THERMOSTAT1. Pull Knob Dial,2. Loosen 1 scr
CIRCUIT DIAGRAM4THERMOS'[A'TYL _ BKGN{GN_L)t <_ BKs_it"__FL_REs_oRP.T.C STARTERYL: YELLOWBK: BLACKBL: BLUEGN:GREENTHE PLUG TYPE ON C
TROUBLESHOOTINGDEFECT EFFECT CAUSE REMEDYGROUP PARTIALLYOR COMPLETELYOUT OFREFRIGERANTCHARGEEXCESSIVELYFULLHUMIDITY IN THESYSTEMPRESENCE OF AIRIN THE
NO COOLINGThe Compressordoesn't run,Check if the currentflows at the contactingPoor contacting pointReplace theThermostat.Check if the current fl